OFFICIAL-SOURCE RECALL · NEW ZEALAND
21 July 2026 Legrand Residual Current Circuit Breaker (safety Recall: ! Legrand is recalling the Residual
Use the identifiers printed on your item to determine whether this recall may affect the product you own.
CHECK THE ITEM YOU OWN
Is your product affected?
- Brand
- See official notice
- Product
- 21 July 2026 Legrand Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P - sold through trade channels
- Manufacturer
- See official notice
- Lot number
- manufacturing, Date, marking, date
- Batch number
- manufacturing, Date, marking, date
- Date code
- 24W24, 24W24 on the product box withou
The barcode may identify the product type, while the recall may apply only to certain lots, dates or variants. Check all identifiers listed in the official recall.
Why this product was recalled
! Legrand is recalling the Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P because of a risk of electric shock and electrocution. An affected unit may fail to trip in response to certain types of fault current (specifically, pulsating DC residual currents), meaning it may not provide the level of electrocution protection indicated by its markings. This is due to a mixed-batch manufacturing issue. Affected units are internally coded as 100mA Type AC rather than 30mA Type A as marked, providing tripping only for residual sinusoidal alternating current, not for residual pulsating DC currents as required. What to do... Electrical professionals should test with an external RCD tester — this is the only reliable field method for confirming whether a unit is affected. Do not use the integrated test button. A faulty unit will fail to trip at 30mA when tested with an external RCD tester. Ensure the test settings are set to 30mA type A. If you are uncertain whether a unit is affected, treat it as affected. If your unit is affected,
Hazard
! Legrand is recalling the Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P because of a risk of electric shock and electrocution. An affected unit may fail to trip in response to certain types of fault current (specifically, pulsating DC residual currents), meaning it may not provide the level of electrocution protection indicated by its markings. This is due to a mixed-batch manufacturing issue. Affected units are internally coded as 100mA Type AC rather than 30mA Type A as marked, providing tripping only for residual sinusoidal alternating current, not for residual pulsating DC currents as required. What to do... Electrical professionals should test with an external RCD tester — this is the only reliable field method for confirming whether a unit is affected. Do not use the integrated test button. A faulty unit will fail to trip at 30mA when tested with an external RCD tester. Ensure the test settings are set to 30mA type A. If you are uncertain whether a unit is affected, treat it as affected. If your unit is affected,
What consumers should do
is a free replacement of affected units." /> An affected unit may fail to trip in response to certain types of fault current (specifically, pulsating DC residual currents), meaning it may not provide the level of electrocution protection indicated by its markings. This is due to a mixed-batch manufacturing issue. Affected units are internally coded as 100mA Type AC rather than 30mA Type A as marked, providing tripping only for residual sinusoidal alternating current, not for residual pulsating DC currents as required.Electrical professionals should test with an external RCD tester — this is the only reliable field method for confirming whether a unit is affected. Do not use the integrated test button. A faulty unit will fail to trip at 30mA when tested with an external RCD tester. Ensure the test settings are set to 30mA type A. If you are uncertain whether a unit is affected, treat it as affected. If your unit is affected,
Official recall notice
21 July 2026 Legrand Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P - sold through trade channels
Agency: Product Safety New Zealand
Official publication date: July 21, 2026
Read the official NZ_PRODUCT_SAFETY recall notice →Scan products you own
Scan products you own once and let RecallGuard monitor future official recalls.
Scan & Monitor Products